PMLedger

Commercial boiler maintenance agreement

Shop plan: $49/mo or $390/yr, no contract

Loaded example: a hotel boiler room with 2 condensing boilers, 4 circulator pumps, 2 indirect water heaters and the expansion tanks and valves.

Equipment on the agreement

Unit typeQtyVisits/yrMin/unitCovered parts/visitRemove

Minutes and visits per unit type are our starting values to get you going. Replace them with yours: your agreement sets the service interval, not this calculator.

Costs and price

$/h

Wages, payroll taxes, workers’ comp, truck and tools spread over productive hours.

$
min

Blank: the highest visit count among the units. One visit services everything due that day.

$
%
%

PMLedger

Agreement profitability

Commercial boilers · sample 12-month agreement

Profitable: above target margin

Net annual price$1,650.00
Annual cost to service$1,151.00
Profit$499.00
Real margin30.24 %
Revenue per tech hour$110.00
Minimum renewal price at 30 %$1,644.29
Break-even price (0 % margin)$1,151.00
Current price per unit per month$13.75
Minimum price per unit per month$13.70
Tech hours per year15.00
Site visits2
Unit services18

Where the cost comes from

On-site labor$751.6765.3 %
Drive time$73.336.4 %
Trip charges$70.006.1 %
Covered parts$256.0022.2 %

Where margin leaks

  • Drive time and trip charges eat 12.5 % of the cost.
  • Every 10 extra minutes per unit costs you $165.00 a year.
Open shop workspace

Where margin leaks in this trade

  • Combustion analysis that drags: with an uncalibrated analyzer and a cold boiler, the first half hour is waiting for steady state.
  • Igniters and burner gaskets: the manufacturer kit goes up every year while the agreement price stays where it was three years ago.
  • Plugged condensate traps: the January lockout call is run the same day and sits on no line of the agreement.
  • Purging and refilling after a valve swap: the tech stays an extra hour waiting for the system to come back to pressure.

Template checkpoints: Boiler

Heating and water · Annual · 90 min

  1. Clean burner, igniter and flame sensor
  2. Clean combustion chamber and heat exchanger
  3. Run a combustion analysis and log CO, CO2 and efficiency
  4. Check system pressure and expansion tank
  5. Inspect relief valve, air vents and isolation valves
  6. Check condensate trap and drain (condensing boilers)
  7. Inspect venting, gaskets and seals
  8. Test safeties, aquastats and controls

Typical PM consumables & parts

Igniter · Burner gaskets · Manufacturer service kit

Suggested trade checkpoints only. Your service agreement sets the interval and scope, not this template.

FAQ

What does it cost to maintain a room with two condensing boilers?

With the loaded example, 18 unit services over 2 site visits a year add up to 15.00 tech hours and $1,151.00 of cost at a $55.00 loaded rate. At $1,650.00 net the real margin is 30.24 %; the floor for 30 % is $1,644.29.

Why two boiler visits a year?

In the example, one before heating season and one mid-season. It is a starting value: whatever you agree with the customer goes in the visits column.

What should go on the service report?

Combustion readings (CO, CO2 and efficiency), system pressure and expansion tank precharge. Next year, you have something to compare against.